Gasoline tank explosion at an oil storage site in Goyang, South Korea

On 7 October 2018, a gasoline storage tank exploded and burned at an oil storage site in Goyang, Gyeonggi Province, South Korea. The site is operated by Daehan Oil Pipeline Corp. About 2.6 million liters of gasoline were reported to have burned, and the fire lasted about 17 hours.

Goyang, Korea
Firefighters struggle to put out a massive blaze on Sunday after an oil tank exploded at a storage station in Goyang, Gyeonggi. [YONHAP]

Police said the fire began when a sky lantern landed in grass about 300 meters from the site. Sparks from the burning grass probably reached oil vapor coming from the tank’s ventilation hatch. Public discussion soon moved from the person who had released the lantern to the safety arrangements at the site.

skylantern
A police spokesperson speaks during a press conference Tuesday. Another officer is holding a sky lantern that police believe caused a fire at an oil storage facility. (Yonhap)

Reports named several weak points. No fire detectors were installed outside the tank, so operators learned of the danger only after about 18 minutes. Vapor recovery devices were not required at oil storage sites. Outside experts inspected the site only once every 11 years, most recently in 2014, and grass grew right next to the tank.

What this case shows. The Goyang fire shows how small a trigger can be: a spark in dry grass was enough, and the delay in detection gave the fire time to grow. In a tank fire the first minutes count most, which is why early detection and a quick start of extinguishing are central to the FoamFatale concept described under details of operation.